Light-type or hybrid-type EPS, method for calculating the capacity in emergency lighting

發(fā)布時(shí)間: 2010/02/24 人氣 :2410

·Light-type or hybrid-type EPS, method for calculating the capacity in emergency lighting

1, when the load is electronic ballast fluorescent lamps, EPS capacity calculation method: EPS capacity = sum of electronic ballast fluorescent lamp power × 1.1;

2, when the load is inductive ballast fluorescent lamps, EPS capacity calculation method: EPS capacity = sum of inductive ballast fluorescent lamp power × 1.5;

3, when the load is the metal halide halid or metal sodium lamps, EPS capacity calculation method: EPS capacity = sum of metal halide or metal sodium lamp power × 1.6.